High-accuracy moisture measurement in SF6 switchgear

Moisture measurement in SF6-insulated switchgear is vital. That?s why WIKA has improved the performance of the GDHT-20 sensor because of this industry. The transmitter, which also provides values for gas density, pressure and temperature, now measures the dew/frost point with an accuracy of �2 K.
Moisture, along with density, is the crucial parameter for assessing the health of the SF6 gas used. The GDHT-20 continuously monitors its content in the gas. The information from the online monitoring forms the input for a downstream trend analysis. The more precise both the density and the moisture measurement are, the more precise this analysis will be.
Predictive maintenance rather than regular maintenance intervals
The model GDHT-20 sensor can be an all-in-one instrument for the online tabs on SF6-insulated switchgear. It works together with three temperature sensors (red), a pressure sensor (blue) and a humidity sensor (yellow).
Competitive shows the operator once the SF6 will reach a critical state so when remedial measures must be taken. Because of this, maintenance work or gas treatment is only undertaken when action is in fact needed. Predictive maintenance thus replaces the sequence of regular maintenance intervals that was previously necessary to avoid ecological and safety risks.
An excessive amount of moisture in the gas compartment is one of these risks. In older plants, moisture mainly increases due to permeation through sealing materials. In younger plant, this is usually due to moisture remaining on metal surfaces or in insulation materials during tank assembly, due to incomplete evacuation before initial filling with SF6.
Excessive moisture content leads to corrosive reaction products that may damage internal components and shorten the service life. If such substances escape, there is yet another danger to people?s health.
SF6 moisture measurement parameters
Measurement of SF6 moisture is therefore indispensable. Typically, the dew or frost point can be used as a parameter. This is the temperature of which the air humidity begins to condense. In the case of SF6, the atmospheric dew point specified by IEC 60376 is -36 �C.
Dollar of the GDHT-20 of �2 K for moisture measurement is validated at the frost point having an internationally valid reference standard. However, the measuring instrument may also be configured for other parameters (dew point, ppmv, ppmw and relative humidity). The new version of the sensor also features greater application flexibility. The GDHT-20 is now also suitable for density monitoring of the alternative insulating gases N2, CF4, O2, CO2 and 3MTM NovecTM 4710.
Note
Further information on the GDHT-20 sensor can be found on the WIKA website. Should you have any questions, your contact will gladly help you.