A diaphragm seal system in a vacuum process must master a significant challenge ? it must deliver a reliable measuring result, even though the pressure drops and the temperature rises simultaneously. The example of a chemical company producing phthalic anhydride (PA) demonstrates it is in no way self-evident that this requirement could be met on a consistent basis.
Unseen is primarily used as a plasticiser for plastics. However, it is also used in the production of synthetic resins and dyes. The plant operator obtains this compound via the catalytic oxidation of o-xylene in the gas phase, accompanied by a vacuum distillation process.
Critical phase for pressure measurement
In this technique, the critical phase for pressure measurement occurs in the distillation column. There, the process temperature can rise to a lot more than 230 �C while the pressure drops to 100 mbar abs. With this type of contrary action, the conventional installed measurement technology reaches its performance limit relatively quickly, which the aforementioned manufacturer was forced to learn ? all instrumentation showed a measurement deviation outside the defined tolerance after only a fortnight.
Diaphragm seal system adapted in every elements to the vacuum process
The diaphragm seal system is tailored exactly to the conditions of the vacuum process and tested under application conditions.
Consequently, the company approached WIKA with the obtain a measuring solution that would also fulfil its task with the required accuracy in the long run beneath the conditions described. WIKA then drew on its in-depth expertise to create a diaphragm seal system for the vacuum process, consisting of an activity transmitter (model IPT-20), a flange-type diaphragm seal with flush diaphragm (model 990.27) and a capillary.
All elements of this measuring system were selected designed for the application. Silicone oil KN32 was therefore selected because the fill fluid for pressure transmission. The cleaning and conditioning of the diaphragm seal, the capillary, the connection pieces as well as the automated filling process were also matched to each other exactly. With sensitive limit ranges, even one drop of liquid too much or too little can destabilise the quantity balance of the diaphragm seal system and therefore impair its function. As a result, correct measurement would no more be guaranteed.
Test under application conditions
After cleaning, all parts of the diaphragm seal system were first fully welded into a single unit as usual, followed by the filling and adjustment of the system. Before delivery, however, there is another crucial step ? in its laboratory, WIKA simulated vacuum pressure process for the diaphragm seal system relative to the client?s conditions and subjected it to a thermal ageing process. This test confirmed the process suitability of the measuring system.
Note
Further information on the WIKA diaphragm seal systems can be found on the WIKA website. In case you have any questions, your contact will gladly help you.
Also read our posts
Diaphragm seals for stable flow measurement in deep seas
How do diaphragm seals work?
Watch the next video for more information about the functionality, application areas and advantages of diaphragm seals: